Approximate Fuel Consumption Chart

Generator Size (kW)
1/4 Load (gal/hr)
1/2 Load (gal/hr)
3/4 Load (gal/hr)
Full Load (gal/hr)
20
0.6
0.9
1.3
1.6
30
1.3
1.8
2.4
2.9
40
1.6
2.3
3.2
4.0
60
1.8
2.9
3.8
4.8
75
2.4
3.4
4.6
6.1
100
2.6
4.1
5.8
7.4
125
3.1
5.0
7.1
9.1
135
3.3
5.4
7.6
9.8
150
3.6
5.9
8.4
10.9
175
4.1
6.8
9.7
12.7
200
4.7
7.7
11.0
14.4
230
5.3
8.8
12.5
16.6
250
5.7
9.5
13.6
18.0
300
6.8
11.3
16.1
21.5
350
7.9
13.1
18.7
25.1
400
8.9
14.9
21.3
28.6
500
11.0
18.5
26.4
35.7
600
13.2
22.0
31.5
42.8
750
16.3
27.4
39.3
53.4
1000
21.6
36.4
52.1
71.1
1250
26.9
45.3
65.0
88.8
1500
32.2
54.3
77.8
106.5
1750
37.5
63.2
90.7
124.2
2000
42.8
72.2
103.5
141.9
2250
48.1
81.1
116.4
159.6

 



Home | Company Profile | Services | Inventory | Links | Site Map | Contact | Used & Surplus Diesel Generators | Transformers
Access Flooring | Fire Suppression | Air Conditioning | Uninterruptible Power Supplies (UPS) | Power Distribution Units (PDU)

We Buy and Sell Liebert & Powerware Used UPS, MGE, and Surplus Uninterruptible Power Supplies.
 

 

 
Critical Power Exchange, LLC
3808 N. Sullivan Rd, Building 29A
Spokane Valley, WA 99216

Toll Free (877) 315-4176
Phone (509) 228-0178
Fax (509) 228-0378
E-Mail info@criticalpower.com
 

Critical Power Exchange, LLC

Copyright © 2006-2010
Critical Power Exchange, LLC
All Rights Reserved

Web Development by
Flytrap Productions