Home > Equipment Descriptions > Power Distribution Units (PDU) > PDU Specs

Power Distribution Units (PDU) - Specifications

The models below have a KVA of 15,
dimensions of  20" x 32" x 68"
and panelboard poles of 42 (standard) and 84 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 15C

575/208

20

550

2,500
PPA 15C

480/208

25

550

2,500
PPD 15C

240/208

50

550

2,500
PPC 15C

208/208

60

550

2,500
PRC 15 (No Xfmr)

208/208

60

300

---

The models below have a KVA of 30,
dimensions of  20" x 32" x 68"
and panelboard poles of 42 (standard) and 84 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 30C

575/208

40

700

4,600
PPA 30C

480/208

50

700

4,600
PPD 30C

240/208

100

700

4,600
PPC 30C

208/208

208

700

4,600
PRC 30 (No Xfmr)

208/208

110

300

---

The models below have a KVA of 50,
dimensions of  32" x 32" x 68"
and panelboard poles of 84 (standard) and 126 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 50C

575/208

70

850

6,200
PPA 50C

480/208

80

850

6,200
PPD 50C

240/208

175

850

6,200
PPC 50C

208/208

200

850

6,200
PRC 50 (No Xfmr)

208/208

175

400

---

The models below have a KVA of 75,
dimensions of  32" x 32" x 68"
and panelboard poles of 84 (standard) and 126 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 75C

575/208

100

1,050

8,100
PPA 75C

480/208

125

1,050

8,100
PPD 75C

240/208

250

1,050

8,100
PPC 75C

208/208

300

1,050

8,100
PRC 75 (No Xfmr)

208/208

300

400

---

The models below have a KVA of 100,
dimensions of  32" x 32" x 68"
and panelboard poles of 84 (standard) and 126 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 100C

575/208

150

1,275

9,900
PPA 100C

480/208

175

1,275

9,900
PPD 100C

240/208

350

1,275

9,900
PPC 100C

208/208

400

1,275

9,900
PRC 100 (No Xfmr)

208/208

350

450

---

The models below have a KVA of 125,
dimensions of  32" x 32" x 68"
and panelboard poles of 84 (standard) and 126 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 125C

575/208

175

1,450

11,500
PPA 125C

480/208

200

1,450

11,500
PPD 125C

240/208

400

1,450

11,500
PPC 125C

208/208

500

1,450

11,500
PRC 125 (No Xfmr)

208/208

450

450

---

The models below have a KVA of 150,
dimensions of  44" x 32" x 68"
and panelboard poles of 126 (standard) and 168 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 150C

575/208

200

1,750

12,500
PPA 150C

480/208

250

1,750

12,500
PPD 150C

240/208

500

1,750

12,500
PPC 150C

208/208

600

1,750

12,500
PRC 150 (No Xfmr)

208/208

600

650

---

The models below have a KVA of 200,
dimensions of  44" x 32" x 68"
and panelboard poles of 126 (standard) and 168 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 200C

575/208

300

2,250

15,500
PPA 200C

480/208

350

2,250

15,500

The models below have a KVA of 225,
dimensions of  44" x 32" x 68"
and panelboard poles of 126 (standard) and 168 (optional).

Model

Input/Output
Voltage

Input Bkr.
(Amps)

Weight (Lbs)

Heat Output
(BTU/HRQ)
PPB 225C

575/208

300

2,250

15,800
PPA 225C

480/208

400

2,250

15,800






Home | Company Profile | Services | Inventory | Links | Site Map | Contact
Used & Surplus Diesel Generators | Access Flooring | Fire Suppression | Transformers
Air Conditioning | Uninterruptible Power Supplies (UPS) | Power Distribution Units (PDU)

 

    Liebert Gold Reseller
Liebert
BOMA International Conference
Liebert
National Demolition Association
Liebert
FMA World Workplace

Critical Power
 
 
 
 
Critical Power Exchange, LLC
23502 E. Knox Suite 2
Liberty Lake, WA 99019

Toll Free (877) 315-4176
Phone (509) 228-0178
Fax (509) 228-0378
E-Mail info@criticalpower.com
 

Critical Power Exchange, LLC

Copyright © 2006-2008
Critical Power Exchange, LLC
All Rights Reserved

Web Development by
Flytrap Productions